Juniper SRX5400 Hardware Manual page 252

Hide thumbs Also See for SRX5400:
Table of Contents

Advertisement

SRX5400 Services Gateway Hardware Guide
226
Table 53: Chassis Component Alarm Conditions on SRX5400, SRX5600,
and SRX5800 Services Gateways (continued)
Chassis
Component
Alarm Condition
Temperature
The chassis temperature has
exceeded 55 degrees C
(131 degrees F), the fans have
been turned on to full speed,
and one or more fans have
failed.
The chassis temperature has
exceeded 65 degrees C
(149 degrees F), and the fans
have been turned on to full
speed.
The chassis temperature has
exceeded 65 degrees C
(149 degrees F), and a fan has
failed. If this condition persists
for more than 4 minutes, the
Services Gateway shuts down.
Chassis temperature has
exceeded 75 degrees C
(167 degrees F). If this
condition persists for more
than 4 minutes, the Services
Gateway shuts down.
The temperature sensor has
failed.
Remedy
Check room temperature.
Check air filter and replace
it.
Check airflow.
Check fan.
Check room temperature.
Check air filter and replace
it.
Check airflow.
Check fan.
Check room temperature.
Check air filter and replace
it.
Check airflow.
Check fan.
Check room temperature.
Check air filter and replace
it.
Check airflow.
Check fan.
Check environmental
conditions and alarms on
other devices.
Ensure that environmental
factors (such as hot air
blowing around the
equipment) are not
affecting the temperature
sensor.
If the alarm recurs, open a
support case using the
Case Manager link at
http:/ /www .juniper .net/support/
or call 1-888-314-5822
(toll free, US & Canada) or
1-408-745-9500 (from
outside the United
States).
Copyright © 2017, Juniper Networks, Inc.
Alarm
Severity
Yellow
Yellow
Red
Red
Red