5.4 Installation for the first time

Air and moisture in the refrigerant system have undesirable effects as below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and
evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come
out, the pipes have leakage.
1. Air purging with vacuum pump
(Indoor unit)
Compound meter
Charge hose
Vacuu
Vacuum
pump
Vacuu
Vacuum
pump
(Liquid side)
(Gas side)
Manifold valve
0.1Mp
-
a
Lo
Hi
Handle Lo
Two-way valve
Three-way valve
Pressu
Pressure
gauge
Handle Hi
Handle Hi
Charge hose
12
(Outdoor unit)
Close
Close