5. Pipe the SVI II AP to the actuator. Ensure:
The airset provides the SVI II AP with at least 5-10 psig more supply pressure than
required by the actuator (maximum spring pressure):
Supply pressure for single acting SVI II AP and AP High Flow:
20 -100 psi (1.4 - 6.9 bar) (138 - 690 kPa)
Supply pressure for double acting SVI II AP:
25 - 150 psi (1.73 - 10.3 bar) (172 - 1030 kPa)
Minimum tubing diameter 1⁄4" (6 mm x 4 mm)
Any other pneumatic accessories are correctly piped without restricting the SVI II AP
output(s) to the actuator.