Operation Instructions

Phase 3 - Defaulting Door Controls

Step Description
All Door Controls should be installed at this point and powered up.
1.
All Door Controls must be defaulted before joining a network.
Note: Door Controls will be shipped with their factory default settings.
Enter Engineer mode on each Keypad Door Control in the following way
A. Press X followed by 6666
B. Enter 55 –to default
C. Press the tick to confirm – the keypad will now go through the
process of defaulting itself.
D. The process could take 20-30 seconds. The LED will flash once every
second when it is complete
E. Repeat the process for all keypad Door Controls
Enter Engineer mode on each Wi-Bio Door Control in the following way
A. Enter 6666
B. Enter 55 –to default
C. Scan Finger to confirm – the Door Control will now go through the
process of defaulting itself.
D. The process could take 20-30 seconds. The LED will flash once every
second when it is complete.
E. Repeat the process for all Wi-Bio Door Controls
Enter Engineer mode on each Prox Only Door Control in the following way
A. Add a programming card to the Door Control by presenting a card
twice on power-up. The security wing must be removed first!
B. Present this new programming card to enter Engineer mode.
C. Present the programming card again to select "Default mode".
D. Present any other card once to default the Door Control.
E. The process could take 20-30 seconds. The LED will flash once every
second when it is complete
Setting up TCP-IP - Static IP
Step Description
1.
Default the Controller. See Restore Factory settings on page 11. The
Controllers default IP address is 169.254.1.1.
2.
Set the Controller address to address 1. See page 11 for details.
3.
Connect the Controller directly to a PC to using an ethernet cable.
Connecting the Controller directly to a PC using default IP address..
4.
Connect an Ethernet cable between the Controller and the PC. (The default
IP address of the Controller is 169.254.1.1)
5.
Set the IP address on the PC to a similar IP address e.g. 169.254.1.2
Note: If there is no LED activity on your PC's ethernet interface then the PC
requires a cross-over cable between the PC and the Controller.
6.
Open the GSDWin application.
On the Controller tab, Select TCP/IP with Static option and enter the
default Controller IP address of 169.254.1.1 and click apply. The
Controller icon will turn blue when it comes online. A new IP address can
then be sent to the Controller using the "Controller TCP/IP Configuration"
button.
Sending a new IP address to the Controller e.g. 192.168.1.26.
7. Make sure the controller is online and click on the
"Controller TCP/IP Configuration" button.
8. Choose Static IP mode and enter the IP address,
Netmask and Default Gateway assigned by your
network administrator. Click "Send new settings
to Controller". The Controller will now go offline as
the new IP Address settings are applied.
9. Connect the PC and Controller to your LAN
and enter the new IP address to allow the
application to communicate with the
Controller.
Note: Reset the IP address on your PC to its
original setting for your LAN.
Operation Instructions