Level Values
Volume Values
Enter up to 32 level breakpoints, where the corresponding volume is
known. The values corresponding to 100% and 0% levels must be entered.
The breakpoints can be ordered from top to bottom, or the reverse.
Example (values are for example purposes only)
2.2.2.6.1.
2.2.2.6.2.
2.2.2.6.3.
Entering breakpoints via the hand-held programmer:
a)
b)
c)
d)
e)
f)
1)
Unit (Level) 2.2.1.6.
See
2)
PV (volume/level) Units 2.2.2. 1 .
See
7ML19985JF02
SITRANS LR250 (PROFIBUS PA) – INSTRUCTION MANUAL
Range: 0.0000 to 999999 (m, cm, mm, ft, in, %)
1)
Default: 0.0
Range: 0.0000 to 999999 (% or volumetric units)
2)
Default: 0.0
Level
Breakpoint
value
number
4
19.5
3
9
2
5
1
0
XY index
X value
Y value
The default for level values is percent: if you want to select units
instead, navigate to Input (2.2.) > Sensor Calibration (2.2. 1 .) > Unit
(Level) (2.2.1.6.), and select the desired unit
Navigate to Input (2.2.) > Volume conversion (2.2.2.) > PV (volume/
level) Units (2.2.2.1.), and select the desired volume units.
Go to XY index (2.2.2.6. 1 .) and enter the number of the breakpoint you
wish to adjust: for example, for breakpoint 1 enter 1.
Go to X value (2.2.2.6.2.) and enter the level value for the breakpoint
just identified.
Go to Y value (2.2.2.6.3.) and enter the volume value for the
breakpoint just identified.
Repeat steps (c) to (e) until values have been entered for all required
breakpoints.
on page 55.
on page 56.
Level
Breakpoint
value
Number
(m)
1
0
2
5
3
9
4
19.5
Volume
value
(l)
0
500
3000
8000
Page 59