14. Detail setting in EEPROM of outdoor unit
Never use the DN code unlisted in the following table.
DN
04
Operation for using snowfall sensor
05
Outdoor fan silent mode
1
0C
Indoor unit drain pump forced operation
Measures against smell when indoor unit cooling
0D
thermostat OFF
1A
Demand 1 current (%)
1B
Demand 2 current (%)
1E
Demand remote controller display
23
E06 ignore function
2A
Dew condensation prevention control of indoor unit
2B
DP operation time for slime measures
3E
PSccutgt delay-start setting
49
Automatic backup mode setting
81
Outdoor unit capacity
8F
High static pressure setting
Item
1 - 50
Setting No.
0=No sensor & control (P)
2=No sensor & no control
(For detail, refer to 5-1-3)
0=Invalid (P)
2=Silent priority & silent mode 2,,,,, 12=Silent mode 12
(For detail, refer to 5-1-4)
0=Invalid
1=stop for 2 hours and drive for 20 min. constantly
2=stop for 20 min. and drive for 20 min. constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
8-11=delay drive when stopped
12-15=Delay drive when thermostat OFF & stopped
(For detail, refer to 6-4)
0=Invalid (P)
1=Measures against smell
0=0%
45=45%,,,,,
140=140%
(For detail, refer to 10-1)
0=0%
45=45% ,,,,,
140=140%
(For detail, refer to 10-1)
0=No demand display
1=When demand ON, "ready to start" display (P)
2=When forced thermostat OFF with demand ON,
"ready to start" display
(For detail, refer to 10-1)
-1=Invalid (P)
1=1 ,,,,,
14 - 52=Never use
(For detail, refer to 13-1)
0=Invalid (P)
2=40 min.
4=60min.
20=20 min
40=40 min.
60=60 min.
(For detail, refer to 6-4)
0=8 second delay-start (P)
1=(system address x1x8) second delay-start
2=(system address x2x8)
3=(system address x3x8)
0=Display (P)
(For detail, refer to 12-1-4)
0=Invalid
1=22
4=32
5=36
8=50
9=56
12=80
13=90
16=125
17=140
20=200
21=224
24=335
25=355
28=500
29=560
32=670
33=710
0=Invalid (P)
2=Never use
4=Never use
6=Never use
(For detail, refer to 5-1-2)
3WAY SYSTEM
Control Functions
(P) : Factory preset mode
1=Sensor & control
3=Sensor & no control
1=Silent mode 1
40=40%
100=100% (P) ,,,,,
-1=No control
40=40%
70=70% (P) ,,,,,
-1=No control
0=0
13=13
1=30 min.
3=50 min.
30=30 min. (P)
50=50 min.
1=non-displayed
2=25
3=28
6=40
7=45
10=63
11=71
14=100
15=112
18=160
19=180
22=250
23=280
26=400
27=450
30=600
31=630
34=800
35=840
1=High static pressure mode
3=Never use
5=Never use