7. Charging Compressor Oil
CAUTION
Vacuum pump
7-3. Charging Additional Compressor Oil (after replacing compressor)
The rated amount of oil is pre-charged in the compressors as given below:
Model name
Compressor model
U-8MF2E8
U-10MF2E8
U-12MF2E8
U-14MF2E8
U-16MF2E8
When replacing a faulty compressor, be sure to first measure the amount of remaining oil in the compressor.
Charge additional new oil equal to the difference in the remaining oil and the rated amount as listed above.
For example: Type of replaced compressor: C-SDN453H8B
Remaining oil in the removed compressor: 2.2
Additional oil to be charged: 2.2 (remaining oil in the removed compressor) – 1.7 (rated oil amount) = 0.5
* If the result is a negative amount (remaining oil in the removed compressor is less than the rated amount), it is not
necessary to discharge the extra oil from the system.
For the method used for additional oil charging after compressor replacement, refer to "7-1. If Refrigerant Has
Already Been Charged to Outdoor Unit."
The oil absorbs moisture readily. This work must be completed quickly.
Manifold gauge
Lo
Hi
Oil
Q'ty
5JD650ZBA22
1
5JD650ZBA22
1
5JD650ZBA22
1
C-SDN453H8B
1
5JD650ZBA22
1
C-SDN453H8B
1
5JD650ZBA22
1
C-SDN523H8B
1
Outdoor Unit Repair Procedures
Fig. 13
Pre-charged amount of oil (liters)
1.6
1.6
1.6
1.7
1.6
1.7
1.6
1.7
2 - 17
3WAY SYSTEM
Low-pressure outlet port
(for ø7.94mm-dia connector)
High-pressure outlet port
(for ø7.94mm-dia connector)
Liquid tube service port
(for ø7.94mm-dia connector)
Discharge tube service port
(for ø7.94mm-dia connector)
Suction tube service port
(for ø7.94mm-dia connector)
Oil balance tube service port
(For 7.94mm-dia. connector)