14. Detail setting in EEPROM of outdoor unit
Never use the DN code unlisted in the following table.
DN
A3
The minimum operating time 1 until defrosting
Measures against smell when indoor unit cooling
A6
thermostat OFF
Validity/invalidity of capacity control when cooling
A7
operation
AC
Actuation of solenoid valve kit (EP closed)
C1
O2 output change
Discharge air temperature control with thermostat
E1
OFF additional time
Item
1 - 51
Setting No.
20=20min..
40=40min. (P)
(For detail, refer to 9-2)
0=Invalid (P)
0=Invalid (P)
0=Invalid (P)
0=Continuously set OFF (P)
1=Refrigerant leak prevention (normal OFF)
2=Refrigerant leak prevention (normal ON)
(For detail, refer to 4-7)
-20=-20 min.
0=0 min. (P) ,,,,,
(For detail, refer to 6-5)
3WAY SYSTEM
Control Functions
(P) : Factory preset mode
21=21min. ,,,,,
41 - 90=Never use
1=Valid
1=Valid
1=Valid
-19=-19 min. ,,,,,
10=10 min.
1