Siemens Simatic ET 200SP Manual page 28

Analog output module aq 2xu/i hs
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Interrupts/diagnostics alarms
5.1 Status and error displays
Meaning of the LEDs
The following table contains the meaning of the status and error displays. Corrective
measures for diagnostics alarms can be found in section Diagnostics alarms (Page 30).
DIAG LED
Table 5- 1
Channel status/channel fault LED
Table 5- 2
Channel status
PWR LED
Table 5- 3
28
Error display of the DIAG LED
DIAG
Meaning
Backplane bus supply of the ET 200SP not OK
Off
Module parameters not assigned
Flashes
Module parameters assigned and no module diagnostics
On
Module parameters assigned and module diagnostics
Flashes
Status/error display of the channel status/channel fault LED
Channel fault
Off
Off
On
Off
Off
On
On
On
Status display of the PWR LED
PWR
Meaning
No supply voltage L+
Off
Supply voltage L+ present
On
Meaning
Channel deactivated or no load voltage L+
Channel activated and no channel diagnostics
Channel activated and channel diagnostics
Not permitted (error)
Analog output module AQ 2xU/I HS (6ES7135-6HB00-0DA1)