Parameter data record
A.2 Parameter assignment and structure of the parameter data record
Codes for output ranges
The table below contains the codes for the output ranges of the analog output module. You
must enter these codes in bytes x+1 of the channel parameter block of data record 128 (see
previous figure).
Table A- 2
Output range
Voltage
±10 V
±5 V
0 to 10 V
1 to 5 V
Current
±20 mA
0 to 20 mA
4 to 20 mA
Codes for substitute values
The table below contains the codes for the substitute values. You must enter these codes in
bytes x+4 and x+5 (see previous figure).
Table A- 3
Output range for
Voltage
±10 V
±5 V
0 to 10 V
1 to 5 V
Current
±20 mA
0 to 20 mA
4 to 20 mA
42
Codes for output ranges
Codes for substitute values
Code
0000 0000
0000 0001
0000 0010
0000 0011
0000 0000
0000 0001
0000 0010
Permitted substitute value
-32512 ... +32511
-32512 ... +32511
0 ... +32511
-6912 ... +32511
-29031 ... +29030
0 ... +29030
-692 ... +29030
Analog output module AQ 2xU/I HS (6ES7135-6HB00-0DA1)
Manual, 09/2016, A5E03576140-AD