Connection: Current output 2-wire connection
The figure below shows the block diagram and an example of the terminal assignment of the
analog output module AQ 2xU/I HS on the BaseUnit BU type A0/A1.
①
2-wire connection for current output
②
Backplane bus interface
③
Microcontroller
④
Digital-to-analog converter (DAC)
⑤
Output conditioner
⑥
Color identification label CCxx (optional)
⑦
Temperature recording for BU type A1 only (func-
tion cannot be used for this module)
⑧
Filter connection supply voltage (only when light-
colored BaseUnit is present)
Q
+
Analog output voltage/current positive, channel n
n
Q
-
Analog output voltage/current negative, channel n
n
Figure 3-1
Wiring and block diagram for current output 2-wire connection
Analog output module AQ 2xU/I HS (6ES7135-6HB00-0DA1)
Manual, 09/2016, A5E03576140-AD
S
+
Sensor cable positive, channel n
n
S
-
Sensor cable negative, channel n
n
RES
Reserve, must remain unused for future func-
tion extensions
L+
24 V DC (infeed only with light-colored Ba-
seUnit)
M
Ground
P1, P2, AUX
Internal self-assembling voltage buses
Connection to left (dark-colored BaseUnit)
Connection to left interrupted (light-colored
BaseUnit)
DIAG
Diagnostics LED (green, red)
AQ0, AQ1
Channel status LED (green)
F0, F1
Channel fault LED (red)
PWR
Power LED (green)
Connecting
3.1 Wiring and block diagram
15