Parity
Word Length
Stop Bits
Duplex (COM1,
COM2, COM 4)
Cable Length
Ethernet
Termination
Protocol
Protocol Modes
8.4
Visual Indicators
COM1,COM2,
COM4
Ethernet LAN
Push-button
8.5
Power Supply
Power Input
AC/DC PWR IN
DC power Input
DC PWR
5 Volt Power
Output
DC power
Output
16Vrms applied
Efficiency
Transient
Protection
SCADAPack 32P Controller Hardware Manual
May 26, 2006
none, even, or odd
7 or 8 bits
1 or 2 bits
full or half with RTS/CTS control
RS-232 –maximum 50 ft (15.2 m)
RS-485 –maximum 4000 ft (1200 m)
RJ-45 modular connector
10BaseT (twisted pair)
10M bits per second.
TeleBUS (compatible with Modbus RTU and Modbus ASCII)
slave, master, master/slave, store and forward
received data
transmitted data
clear to send
data carrier detect
Ethernet network receive or transmit data
Ethernet port connected to a network
I/O module LED power status LED
Status LED (shows functional status)
5V power LED (LED power not applicable)
Run LED
Forced I/O LED
Counter Inputs 0, 1, 2 and 3 LEDs
LED power toggle
16Vrms ±20%
13 to 24Vdc nominal
30Vdc maximum
30V maximum
10.7V typical turn on
9V typical turn off
5V at 1.3A capacity
5V at 500 mA required by SCADAPack 32P
20-24V with 1.0Vp-p maximum ripple.
300mA available at 5V/0.5A, de-rate linearly to 100mA
available at 5V/1.3A
80%, 12V on DC PWR input
Transient: 2.5kV surge withstand capability as per ANSI/IEEE
C37.90.1-1989
(RxD) LED
(TxD) LED
(CTS) LED
(DCD) LED
LAN LED
LINK LED
38
Need help?
Do you have a question about the SCADAPack 32P and is the answer not in the manual?