3-7 Dwell Timer

3-7 Dwell Timer
Output 2 can be configured as dwell timer by selecting TIMR for
OUT2. As the dwell timer is configured, the parameter SP2 is used
for dwell time adjustment. The dwell time is measured in minute
ranging from 0.1 to 4553.6 minutes. Once the process reaches the set
point the dwell timer starts to count down until zero ( time out ). The
timer relay will remain unchanged until time out. The dwell timer
operation is shown as following diagram.
After time out the dwell timer will be restarted by pressing the RESET
key.
The timer stops to count during the manual control mode, failure
mode, calibration period and auto-tuning period.
PV
SP
ALM
ON
OFF
If output 2 is configured as dwell timer, ALMD will be hidden.
If output 2 is configured as dwell timer, ALMD will be hidden.
SP3
Timer starts
Figure 3.6 Dwell Timer Function
Figure 3.6 Dwell Timer Function
UM0C911A
power off or
touch RESET key
Time
Time
42