Control Outputs - Brainchild C21 User Manual

Auto-tune fuzzy / pid process / temperature controller
Table of Contents

Advertisement

process value
INHI
PV
INLO
SL
Formula : PV = INLO + ( INHI INLO )
Formula : PV = INLO + ( INHI INLO )
Example : A 4-20 mA current loop pressure transducer with range
Example : A 4-20 mA current loop pressure transducer with range
0 - 15 kg/cm is connected to input, then perform the
0 - 15 kg/cm is connected to input, then perform the
following setup :
following setup :
INPT = 4 - 20
INPT = 4 - 20
INHI = 15.00
INHI = 15.00
Of course, you may select other value for DP to alter the
Of course, you may select other value for DP to alter the
resolution.
resolution.

3-3 Control Outputs

3-3 Control Outputs
There are 4 kinds of control modes can be configured as shown in
Table 3.1
Table 3.1
Table 3.1 Heat-Cool Control Setup Value
Table 3.1 Heat-Cool Control Setup Value
Control
Modes
Heat only
Cool only
Heat: PID
Cool: ON-OFF
Heat: PID
Cool: PID
: Don't care
:Adjust to met process
requirements
input signal
S
SH
2
INLO = 0.00
INLO = 0.00
DP = 2-DP
DP = 2-DP
OUT1
OUT2
REVR
DIRT
REVR
DE.HI
REVR
COOL
Figure 3.1
Figure 3.1
Conversion Curve for
Conversion Curve for
Linear Type Process Value
Linear Type Process Value
S SL
S SL
SH
SH
SL
SL
O1HY
O2HY
:Required if ON-OFF control
is configured
UM0C911A
CPB
DB
34