Slave Diagnostics
Byte
Bit
4
1: Function not supported, e.g. changing
the DP address of the DP/AS-i Link 20E
module by the DP master.
5
1: The DP master cannot interpret the
response from the DP/AS-i Link 20E
module correctly.
6
1: The DP/AS-i Link 20E detects an
incorrect parameter assignment frame
(e.g. incorrect length, incorrect ID number,
incorrect parameters).
7
1: The DP/AS-i Link 20E module was
assigned parameters by a different DP
master from the DP master that currently
has access to the DP/AS-i Link 20E
module.
Station Status 2
Byte
Bit
1
0
1: The DP/AS-i Link 20E module must have parameters reassigned by the DP
master.
1
1: A static diagnostic message exists.
2
1 :This bit is always '1' with the DP/AS-i Link 20E module.
3
1: The response monitoring of the DP/AS-i Link 20E module is activated.
4
1: The DP/AS-i Link 20E module has received the"FREEZE" control command.
5
1: The DP/AS-i Link 20E module has received the"SYNC" control command.
6
0: This bit is always set to '0'.
7
1: The DP/AS-i Link 20E module is deactivated, in other words it is not taking
part in the current processing.
Station Status 3
Byte
2
Station status 3 is reserved and is irrelevant for diagnostics on the DP/AS-i Link 20E module.
128
Value/meaning
Value/meaning
Value/meaning
Remedy
Check the configuration.
Check the PROFIBUS.
Check the configuration.
This bit is always 1 if, for example, you
are accessing the DP/AS-i Link 20E
module with a PG or a different DP
master. The DP address of the parameter
assignment master is in the diagnostic
byte"Master PROFIBUS Address".
DP/AS-Interface Link 20E
C79000-G8976-C138–04
Release 11/2002