3.3.10

Set_LPS

Purpose of the Command
With this call, the list of configured AS-i slaves is transferred for permanent storage
in the EEPROM of the master.
When this command is executed, the AS-i master changes to the offline phase and
then changes back to the normal mode (warm restart on the AS-i master).
The call is not executed in the protected mode.
Note
If you use CPUs from the SIMATIC S7 system as the PROFIBUS DP master, then
dependent on the configuration in STEP 7, these may send a complete AS-i slave
configuration to the DP/AS-i Link 20E during the DP startup. Use of the call
described here is then generally unnecessary.
Structure of the Job Data in the Send Buffer
Byte
Bit 7
Bit 6
0
1
2
irrelevant
Slave 1
3
Slave 8
Slave 9
4
Slave 16
Slave 17
5
Slave 24
Slave 25
6
irrelevant
Slave 1B
7
Slave 8B
Slave 9B
8
Slave
Slave
16B
17B
9
Slave
Slave
2B4
25B
The bits in the LPS data have the following meaning: 0: AS-I slave not configured
1: AS-I slave configured.
DP/AS-Interface Link 20E
Release 11/2002
C79000-G8976-C138–04
Meaning
Bit 5
Bit 4
Bit 3
Command number 29
00H
Slave 2
Slave 3
Slave 4
Slave 10
Slave 11
Slave 12
Slave 18
Slave 19
Slave 20
Slave 26
Slave 27
Slave 28
Slave 2B
Slave 3B
Slave 4B
Slave
Slave 11B
Slave
10B
12B
Slave
Slave
Slave
18B
19B
20B
Slave
Slave
Slave
26B
27B
28B
Using the Command Interface
Bit 2
Bit 1
H
Slave 5
Slave 6
Slave 13
Slave 14
Slave 21
Slave 22
Slave 29
Slave 30
Slave 5B
Slave 6B
Slave
Slave
13B
14B
Slave
Slave
21B
22B
Slave
Slave
29B
30B
Bit 0
Slave 7
Slave 15
Slave 23
Slave 31
Slave 7B
Slave
15B
Slave
23B
Slave
31B
91