Table 2 -- ElectricHeater D atafor Unitswith PSC Motor(cent)
UNIT
HP
FLA
40UV, UH075
(at 7 59 Cfm)
1/5
NOMINAL
NUMBER
OF
V/Ph/Hz
ELEMENTS
3
4
208/1/60
5
6
3
4
240/1/60
5
6
3
4
277/1/60
5
6
3
4
208/3/60
5
6
3
4
240/3/60
5
6
3
4
460/3/60
5
6
LEGEND
DX
--
Direct Expansion
FLA
--
Full LoadAmps
LAT
--
Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA
--
Unit Minimum Circuit Ampacity
MOCP --
Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC
--
Permanent Split Capacitor
23.7
30.9
38.1
45.3
27.0
35.3
43.7
52.0
23.3
30,5
37.7
44.9
14.5
21.7
27.0
27.9
16.5
24.8
30.9
30.9
8,2
12.3
15.4
15,4
I-AT
(F)
89
96
102
108
96
104
113
121
96
104
113
121
89
96
102
108
96
104
113
121
96
104
113
121
NOTES:
TOTAL
MCA
MOCP
CAPACITY
(kW)
29.6
30
4.5
38.6
40
6.0
47.6
50
7.5
56.7
60
9.0
33.8
35
6.0
44.2
45
8.0
54.6
60
10.0
65.0
70
12.0
29.1
30
6.9
38.1
40
8.0
47.1
50
10.0
56.2
60
12.0
18.2
20
4.5
27.2
30
6.0
33.8
35
7,5
33,8
35
9,0
20.6
25
6.0
31.0
35
8.0
38.6
40
10.0
38.6
40
12.0
10.2
15
6.9
15.4
20
8,0
19.2
20
19.0
19.2
20
12.0
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coils used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.