Mitsubishi Heavy Industries FDT28KXE6A Service Manual page 94

Inverter driven multi-indoor unit climate control system
Hide thumbs Also See for FDT28KXE6A:
Table of Contents

Advertisement

Error code
E49
Remote controller:
E49
7-segment display:
1. Applicable model
Outdoor unit
2. Error detection method
Detection of anomalously low
pressure
3. Condition of error displayed
• At start up after power on:
When the low pressure sensor
detects lower than 0.003MPa
for 60 seconds continuously.
And if this anomaly occurs 2
times.
• During operation:
When the low pressure sensor
detects 0.134MPa or lower
for 30 seconds coninuously.
And if this anomaly occurs 5
times within 60 minutes
4. Presumable cause
• Low pressure sensor (PSL)
anomaly
• Service valves closed
• EEV anomaly (EEV closed)
• Insufficient refrigerant
amount
• Clogging at EEV or strainer
Note:
Check whether the indoor unit is connected to other outdoor superlink network.
If the error does not recur, connect the Mente PC and continue to collect data.
LED
Green
Red
Keeps flashing Stays Off
Indoor
Keeps flashing 1 time flash
Outdoor
5. Troubleshooting
Diagnosis
Save data for 30 minutes before stopping in Mente PC
Reset power supply and restart.
error occur immediately after
NO
Does the low
pressure fluctuate after the
startup?
YES
characteristics is shown in
Is the opening
degree of EEV for
evaporator side
flucturing?
YES
Is the checked
result of harness and insulation
of EEV coil OK?
YES
Does the
EEV operate
normally by judging
from Mente PC
data, etc?
YES
92
Content
Low pressure anomaly
Does the
YES
the startup?
Is the
NO
connection of
sensor connector
OK?
YES
Are the
sensor characteristics
OK?*
* The sensor
YES
page 94
Is the
NO
connection of
thermistor connector for
heat exchanger
OK?
YES
Are the thermistor
characteristics OK?
YES
NO
Isn't EEV
NO
or strainer
clogged?
NO
Countermeasure
Check and save the data of
operating conditions
Check error status.
Is the refrigerant amount
OK?
Check additional refrigerant
amount charged at site
according to the piping
length instructed on the
label pasted on the panel of
the unit.
Check whether the service
valves are open.
NO
Correct the connection
of low pressure sensor
connector
NO
Replace low pressure
sensor.
Replace outdoor control
PCB.
NO
Correct the connection of
temperature thermistor
connector of heat
exchanger
Replace temperature
NO
thermistor of heat
exchanger at evaporator
side.
Replace control PCB at
evaporator side.
Replace EEV coil.
YES
Replace EEV main body or
strainer.
Check for short circuit of
airflow of heat exchanger
at evaporator side and for
fan motor anomaly