Mitsubishi Heavy Industries FDT28KXE6A Service Manual page 107

Inverter driven multi-indoor unit climate control system
Hide thumbs Also See for FDT28KXE6A:
Table of Contents

Advertisement

I Function of Dip switch for control (SW3, 4, 5)
• SW3 (Function setting)
Switch
ON
Inspection LED reset
SW3-1
OFF Normal
ON
Auto
SW3-2
OFF Normal
ON
Refrigerant quantity check
SW3-4
OFF Normal
ON
Check operation
SW3-5
OFF Normal
ON
Forced cooling/heating
SW3-7
OFF Normal
I Function of Jumper wire (J13, 15)
(With: Shorted / None: Opened)
Jumper
With
External input
J13
None
External input
With
Defrost time
J15
None
Defrost time
• SW4 (Model selection)
Switch
1
Model
FDC335
OFF
FDC400
OFF
FDC450
ON
FDC504
OFF
FDC560
ON
FDC615
OFF
FDC680
ON
• SW4 (Change demand ratio)
ON/OFF
OFF Compressor capacity 60%
ON
ON Compressor capacity 0%
SW4-5
SW4-6
OFF Compressor capacity 80%
OFF
ON Compressor capacity 40%
• SW4 (Master/Slave setting)
ON/OFF
OFF
Master
SW4-7
ON
Slave
Function
Function
Level input
Pulse input
Normal
Cold weather region
SW4
2
3
4
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
Function
Function
-
105
• SW5 (Function setting)
ON/OFF
ON
Test run switch
SW5-1
OFF
Test run switch
ON
Test run operation mode Cooling
SW5-2
OFF
Test run operation mode Heating
ON
Pump down switch
SW5-3
OFF
Pump down switch
ON
Super Link protocol : Previous SL
SW5-5
OFF
Super Link protocol : New SL
• SW7,8,9 (Function setting)
Switch
SW7 Data erase/data write
SW8 7-segment display No. UP
SW9 7-segment display No. UP
-
Function
test run
Normal
Pump down
Normal
Function
order of 1
order of 10