Code
Write-in contents
No.
41
Inverter CM2 operation frequency
42
Answer Hz total
43
Compressor 1 cumulative operating time (estimate)
44
Compressor 2 cumulative operating time (estimate)
45
Compressor 1 start times
46
Compressor 2 start times
47
Compressor stop causes
48
Compressor stop causes
49
Compressor stop causes
50
Compressor stop causes
51
Control status
52
Control status
53
Discharge pressure saturation temperature
54
Intake pressure saturation temperature
55
Control status equal oil 2
56
Control status oil return
57
Control status defrost conditions
Data write-in
Number of
Write-in unit
range
bytes
0~255
1Hz
1
0~65535
1Hz
2
0~65535
1 h
2
0~65535
1 h
2
0~65535
20 times
2
0~65535
20 times
2
1
1
1
1
0~180
1 second
1
0~180
1 second
1
-50~70
0.1ºC
2
-50~70
0.1ºC
2
0,1
1
0~2
1
0~3
1
40
-
-
Record data
Contents
Bit0
Defective outdoor temperature thermistor
Bit1
Defective outdoor unit heat exchanger 1 thermistor
Bit2
Defective outdoor unit heat exchanger 2 thermistor
Bit3
Defective outdoor unit heat exchanger 3 thermistor
Bit4
Defective outdoor unit heat exchanger 4 thermistor
Bit5
Defective discharge pipe thermistor 1
Bit6
Defective discharge pipe thermistor 2
Bit7
Defective sub-cooling coil thermistor 1
Bit0
Defective sub-cooling coil thermistor 2
Bit1
Defective suction pipe thermistor
Bit2
Defective low pressure sensor
Bit3
Defective high pressure sensor
Bit4
Inverter 1 anomalous communication
Bit5
Inverter 2 anomalous communication
Bit6
Anomalous high pressure
Bit7
Anomalous Low pressure
Bit0
Td1 Anomalous discharge pipe temp.
Bit1
Td2 Anomalous discharge pipe temp.
Bit2
CM1 starting defect
Bit3
CM2 starting defect
Bit4
Synchronous failure of CM1
Bit5
Synchronous failure of CM2
Bit6
Current cut of CM1
Bit7
Current cut of CM2
Bit0
Power transistor 1 overheating
Bit1
Power transistor 2 overheating
Bit2
FM01 anomaly
Bit3
FM02 anomaly
Bit4
Compressor stop command from indoor unit
Bit6
Dilution rate protection
Bit7
Demand control 0%
CM1 3-minute delay timer
CM2 3-minute delay timer
0
None
1
Under control
0
None
1
Waiting for oil return
2
Under oil return
0
None
1
Temperature conditions
2
Strengthening temperature conditions
3
Time conditions