(b) 7-Segment display
Code
Contents of display
No.
Unusual code
Pump down
Ð
Check mode
Outdoor unit setup, piping cleaning
00
CM1 operating frequency
01
CM2 operating frequency
02
Tho-A Outdoor air temp.
03
Tho-R1 Heat exchanger temp. 1 (Exit. Front)
04
Tho-R2 Heat exchanger temp. 2 (Exit. Rear)
05
Tho-R3 Heat exchanger temp. 3 (Entrance. Front)
06
Tho-R4 Heat exchanger temp. 4 (Entrance. Rear)
07
Tho-D1 Discharge pipe temp. (CM1)
08
Tho-D2 Discharge pipe temp. (CM2)
10
Tho-C1 Under-dome temp. (CM1)
11
Tho-C2 Under-dome temp. (CM2)
12
Tho-P1 Power transistor temp. (CM1)
13
Tho-P2 Power transistor temp. (CM2)
14
Tho-SC Sub-cooling coil temp.1
15
Tho-SC Sub-cooling coil temp.2
16
Tho-S Suction pipe temp.
17
Cooling operation super cooling
18
Super heat
19
Super heat of sub-cooling coil
20
CT1 Current (CM1)
21
CT2 Current (CM2)
22
EEVH1 Heating expansion valve opening angle
23
EEVH2 Heating expansion valve opening angle
Opening angle of EEVSC overcooling coil
24
expansion valve
26
FM01 Number of rotations
Data display
Minimum
range
units
E??
PoE, PoS
CH?, PCL?
OPE??
0~130
1Hz
0~130
1Hz
L,-20~43
1°C
L,-25~73
1°C
L,-25~73
1°C
L,-25~73
1°C
L,-25~73
1°C
L,31~136
1°C
L,31~136
1°C
L,5~90
1°C
L,5~90
1°C
L,31~136
1°C
L,31~136
1°C
L,18~73
1°C
L,-25~73
1°C
L,-25~73
1°C
0~50
1°C
0~50
1°C
0~20
1°C
SHS
0~70
1A
0~70
1A
0~500
1 Pulse
0~500
1 Pulse
0~500
1 Pulse
0~1500
-1
10 min
33
-
-