Error code
None
Remote controller:
7-segment display:
1. Applicable model
All models
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Wrong connection or breakage
of connecting wires
• Blown fuse
• Transformer anomaly
• Indoor power PCB anomaly
• Broken harness
• Indoor control PCB anomaly
Note:
LED
Green
Red
Stays Off Stays Off
Indoor
Stays Off 2 time flash
Outdoor
5. Troubleshooting
Diagnosis
Is
AC 220-240V/220V
detected between L-N on
the indoor terminal
block?
YES
Note (1)
FDT and FDTC series: F200, F201
Other than FDT and FDTC: Fuse between wires
(1)
Are fuses OK?
(2 pcs)
YES
Other than FDT and
FDT and FDTC series
FDTC series
Is DC18V or higher
detected between Red-
Red (CNW2) at the
transformer secondary
side?
55
–
Power supply system anomaly
Content
(Power supply to indoor unit PCB)
NO
Is AC
380/415 V for 3-phase
unit detected between L1, L2, and L3 on
the outdoor terminal block
respectively.
NO
(2)
Is power
supply between ➀ - ➂ of
CNW0 OK?
Note (2)
Remove
YES
transformer for
other than FDT and
FDTC series (CNW1)
(3)
Is power
supply to FM, LM and etc.
OK?
Note (3) LM: Louver motor
FM: Fan motor
(4)
Is
DC5V detected
between ➃ - ➄ of
CNW2?
Note (4)
➄
–
Countermeasure
Outdoor Noise filter PCB
NO
anomaly Replace it
Wrong wiring or broken
YES
wires between outdoor and
indoor units
Indoor power PCB
NO
anomaly Replace it
Replace FM, LM and etc.
YES
Replace fuse
NO
Indoor power PCB anomaly
NO
Replace it
for GND
Indoor control PCB
YES
anomaly Replace it
Replace transformer
NO
Indoor control PCB
YES
anomaly Replace it