Error code
E30
Remote controller:
E30
7-segment display:
1. Applicable model
Outdoor unit
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Indoor control PCB anomaly
• Outdoor control PCB anomaly
Note:
LED
Green
Red
Keeps flashing Stays Off
Indoor
Keeps flashing 1 time flash
Outdoor
5. Troubleshooting
Diagnosis
wiring connection between
indoor and outdoor units
between L1-L2, L2-L3
and L3-L1 at the terminal block on
outdoor unit AC380/415V
between L1-N at the terminal
block on indoor unit
77
Content
Unmatch connection of
indoor and outdoor unit
Is the
NO
correctly?
YES
Is the voltage
NO
respectively?
YES
Is
the voltage
NO
AC220/240V?
YES
Countermeasure
Correct the wiring
Replace outdoor control
PCB
Disconnection or breakage
of wire between indoor and
outdoor unit
Replace indoor unit PCB