Ambient Conditions; Application Environment; Ambient Temperature; Mounting Position - Siemens SIRIUS 3RM1 Manual

Load feeders and motor starters
Table of Contents

Advertisement

4.5

Ambient conditions

4.5.1

Application environment

The 3RM1 motor starters are designed for use in enclosed spaces in which no severe
operating conditions prevail (e.g. dust, caustic vapors, hazardous gases).
If they are to be installed in dusty or damp rooms, suitable control cabinets must be
provided.
Note
If you operate the 3RM1 motor starter in a control cabinet, ensure that the cabinet is
adequately ventilated.
4.5.2

Ambient temperature

The 3RM1 motor starter has been designed for use under ambient temperatures ranging
from -25 °C to +40 °C, singly in a vertical mounting position, and without a reduction in the
permissible rated operational current. With the deratings given in the section "Rated
operational current (Page 57)", you can operate the 3RM1 motor starters at ambient
temperatures of up to 60 °C.
4.5.3

Mounting position

Installation on a vertical mounting surface is recommended for the 3RM1 motor starter.
Please observe the power reduction levels/deratings for other mounting positions given in
the section "Rated operational current (Page 57)".
SIRIUS 3RM1 motor starter
Manual, 06/2016, A5E0345285095020A/RS-AE/005
Configuration
4.5 Ambient conditions
63

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sirius 3rm10Sirius 3rm11Sirius 3rm12Sirius 3rm13

Table of Contents