Number Of Starting Operations - Siemens SIRIUS 3RM1 Manual

Load feeders and motor starters
Table of Contents

Advertisement

Technical data

9.6 Number of starting operations

9.6
Number of starting operations
Permissible number of starting operations per hour 1/h
Parameter: on-load factor = 50 %
The number of starting operations 1/h is calculated for an effective motor current of 100 %,
and the motor starter's actual performance can be higher.
Motor starter
Max. rated operating current I
Motor
Starting current
Starting time
250 %
400 %
400 %
400 %
500 %
500 %
500 %
600 %
600 %
600 %
700 %
700 %
700 %
144
3RM1.07...
7 A
e
100 ms
1000
100 ms
1000
300 ms
400
500 ms
220
100 ms
750
300 ms
250
500 ms
150
100 ms
500
300 ms
150
500 ms
100
100 ms
360
300 ms
100
500 ms
60
3RM1.02...
3RM1.01...
2 A
0.5 A
3300
1000
400
220
750
250
150
500
150
100
360
100
60
Manual, 06/2016, A5E0345285095020A/RS-AE/005
Unit
3600
1/h
1000
1/h
400
1/h
220
1/h
750
1/h
250
1/h
150
1/h
500
1/h
150
1/h
100
1/h
360
1/h
100
1/h
60
1/h
SIRIUS 3RM1 motor starter