Marstair DXD(H) 50 Installation Instruction

Marstair DXD(H) 50 Installation Instruction

566 series fan coil units

Advertisement

Quick Links

Heronhill - for all your Marstairs requirements
INSTALLATION INSTRUCTION
566 SERIES DXD/H FAN COIL UNITS
56608008-03
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807

Advertisement

loading

Summary of Contents for Marstair DXD(H) 50

  • Page 1 Heronhill - for all your Marstairs requirements INSTALLATION INSTRUCTION 566 SERIES DXD/H FAN COIL UNITS 56608008-03 Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807...
  • Page 2 Heronhill - for all your Marstairs requirements GENERAL TEV Ltd recommend that personnel working on this equipment be skilled and fully conversant with the appropriate Air Conditioning, Refrigeration and Electrical practices and have sound knowledge of current Industrial Safe Working practices. These units are supplied with a holding charge of oxygen free nitrogen and polyolester oil.
  • Page 3 Heronhill - for all your Marstairs requirements DXD/H SPR FAN COIL UNIT INSTALLATION DXD/H fan coil units are designed to be installed within a ceiling void. Air discharge should be via insulated ducting, connected to 250mm diameter spigots (200mm diameter spigots also available) and to appropriately sized discharge plenums/grilles.
  • Page 4: Unit Dimensions

    2. A maximum of 30pa resistance is allowed (total of inlet and discharge added together). DIMENSIONAL INFORMATION UNIT MODEL Dim ‘A’ Dim ‘B’ SPIGOTS WEIGHT (Approx Kg) DXD(H) 50 DXD(H) 60 DXD(H) 90 1230 1195 2-3-4 DXD(H) 130 1430 1395...
  • Page 5 FLC (Amps) S.C. (Amps) Specific Fan Power N.R. A’flow MODEL (l/s) GUIDE EC/DC EC/DC EC/DC EC/DC 0.57 0.46 1.71 1.38 0.58 0.33 DXD(H) 50 0.59 0.53 1.77 1.59 0.58 0.36 0.65 0.60 1.95 1.80 0.66 0.40 0.65 0.60 1.95 1.80 0.69 0.35...
  • Page 6 Heronhill - for all your Marstairs requirements RECOMMENDED FUSE SIZES (Amps) Model STANDARD STANDARD + Electric Heating DUCTWORK Connect discharge ductwork to the spigots provided. Spigot positions are shown below. Spigots are designed to accept 250mm diameter ducting (200mm diameter spigots are available as an option). The installation engineer must ensure that insulated ducting is used and that the complete spigot exterior is insulated up to the unit casing to prevent condensation forming.
  • Page 7: Maintenance

    Heronhill - for all your Marstairs requirements DIP switches at the bottom rear of the controller can be set on site to suit the application. DIP switch Function ON position OFF position Fan control Fan control is temperature dependent in all Fan control in normal operation is operating modes temperature independent...
  • Page 8 Heronhill - for all your Marstairs requirements Tel: +44 (0) 1484 405630. Fax: +44 (0) 1484 405620. Email: sales@quartz.co.uk Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807...