b. If the outer surface of the screen is covered with non-conductive
material (figure below)
the screen turned visible
Cable screen
- Cut the screen in the middle of the bare part. Be careful not to
cut the conductors.
- Turn the conductive surface of the screen visible.
- Cover the turned screen and the stripped cable with copper foil
to keep the shielding continuous. Note: The earthing wire (if
present) must not be cut.
- Push the two parts of the lead-through plate together such that
the EMI conductive cushions press tightly round the screen.
5. Lock the two parts of the lead-through plate by tightening the
position screws .
6. Connect the control cables in appropriate terminal to NIOC/NIOCP
board (or optional terminal block X2/2TB, or other options on the
DIN rail). Refer to Appendix A and Firmware Manual . Tighten
screw to secure connection. Connect the twisted screen (as short
as possible) to the earthing rail
7. Close the cabinet door if no other cables are to be connected.