ABB ACS 600 Hardware Manual page 32

Frequency converters 55 to 630 kw (75 to 700 hp)
Hide thumbs Also See for ACS 600:
Table of Contents

Advertisement

Chapter 3 – Electrical Installation
Cable shield
PE terminal
Strain relief
Strip this part of
the cable
Mains and Motor Cable
Connections
3-8
EMC sleeve
9. Earth the other end of the mains cable screen at the distribution
board.
10. Earth the motor cable screen 360 degrees on the motor side.
11. Connect the additional PE conductors (if present) of the mains and motor cables
to the PE terminal of the cabinet.
12. Connect the separate PE conductor (if used) to the PE terminal of the cabinet.
13. Connect the phase conductors of the mains cable to the U1, V1
and W1 terminals and the phase conductors of the motor cable to
the U2, V2 and W2 terminals.
14. Check that the earthing is still OK.
15. Close the hinged assembly plate.