Upon completion of wire connection, double check it and then connect the power supply.
An all-pole disconnection device which has at least 3mm separation distance in all pole and a
residual current device (RCD) with the rating of above 10mA shall be incorporated in the fixed
wiring according to the national rule.
The appliance shall be installed in accordance with national wiring regulations.
7.2 Specifications of power supply
Medium static pressure duct:
Type
Model
Power
Switch capacity of the
main power supply / Fuse
Indoor unit power cable
Outdoor unit power cable
Connective wire of indoor
and outdoor unit
Wired controller
connective wire
Type
Model
Power
Switch capacity of the main
power supply / Fuse
Indoor unit power cable
Outdoor unit power cable
Connective wire of indoor
and outdoor unit
Wired controller connective
wire
87
Duct type indoor unit
MTA-76C(H)RN1
MTA-150CRN1
220-240V~, 1Ph, 50Hz
20A/8A
2
3×2.5mm
(Includes grounded wire)
\
4×1.0mm
2×1.0mm
2
5×0.5mm
(Shield wire)
Indoor unit
MTA-96C(H)RN1
220-240V~, 1Ph, 50Hz
20A/8A
2
3×2.5mm
(Includes grounded wire)
\
4×1.0mm
2×1.0mm
2
5×0.5mm
(Shield wire)
MOV-76C(H)N1-C
380~415V~, 3Ph, 50Hz
20A/12A
Single unit: 5×6mm
Power-main unit: 5×10mm
Main-auxil unit: 5×6mm
2
(Cooling & heating)
2
(Cooling only)
MOV-96C(H)N1-C
380~415V~, 3Ph, 50Hz
2
(Cooling & heating)
2
(Cooling only)
MCAC-UTSM-201501
Outdoor unit
60A/40A
/
2
2
2
\
Outdoor unit
60A/40A
/
2
5×6.0mm
\