Wiring Connection Of Fv Fan Coil Wiring Harness - Carrier FV4C Installation Instructions Manual

Table of Contents

Advertisement

16---IN PLUG ON WIRING HARNESS TO MOTOR
Pin on
16---Pin
Plug
1
Common
2
W1
3
Common
4
On/Off Delay Selection
5
AC/HP Size Selection
6
Y1
AC/HP CFM Adjust
7
Selection
8
Not Used
9
System Type Selection
10
Dehumidify
11
Aux Heat Size Selection
12
24v AC
13
W2
14
Y/Y2
15
G
16
Not Used
*
Check voltages with 16 ---Pin Plug disconnected from motor.
** These signals will start motor.
PURONR (R- -410A) QUICK REFERENCE GUIDE
S Puron refrigerant operates at 50- -70 percent higher pressures than R- -22. Be sure that servicing equipment and replacement
components are designed to operate with Puron
S Puron refrigerant cylinders are rose colored.
S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose when
charging into suction line with compressor operating
S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low- -side retard.
S Use hoses with 700 psig service pressure rating.
S Leak detectors should be designed to detect HFC refrigerant.
S Puron, as with other HFCs, is only compatible with POE oils.
S Vacuum pumps will not remove moisture from oil.
S Do not use liquid- -line filter driers with rated working pressures less than 600 psig.
S Do not leave Puron suction line filter driers in line longer than 72 hours.
S Do not install a suction- -line filter drier in liquid line.
S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S POE oils may cause damage to certain plastics and roofing materials.
S Wrap all filter driers and service valves with wet cloth when brazing.
S A factory approved liquid- -line filter drier is required on every unit.
S Do NOT use an R- -22 TXV.
S If indoor unit is equipped with an R- -22 TXV or piston metering device, it must be changed to a hard shutoff Puron TXV.
S Never open system to atmosphere while it is under a vacuum.
S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter
driers. Evacuate to 500 microns prior to recharging.
S Do not vent Puron into the atmosphere.
S Do not use capillary tube coils.
S Observe all warnings, cautions, and bold text.
S All indoor coils must be installed with a hard shutoff Puron TXV metering device.
Table 7 – Wiring connection of FV Fan Coil Wiring Harness
Description
Auxiliary Heat Stage 1
Low Speed AC or HP
Auxiliary Heat Stage 2
Single Speed AC or HP ,
High Speed 2--- Speed
AC or HP
Fan
WIRING HARNESS CONNECTION TO EASY SELECT BOARD
Pin on 12---Pin Plug or
Set---up Selection
Pin 9 on PL --- 1
Pin 7 on PL --- 1
Pin 10 on PL --- 1
On/Off Delay Selection
AC/HP Size Selection
Pin 3 on PL --- 1
AC/HP CFM Adjust
Selection
N/A
System Type Selection
Pin 12 on PL --- 1
Aux Heat Size Selection
Pin 8 on PL --- 1
Pin 4 on PL --- 1
Pin 2 on PL --- 1
Pin 1 on PL --- 1
N/A
17
Signal on Pin with
Screw Terminal
Wire Color
Jumpered to R*
Brown
Violet
24VAC**
Orange
White
Blue
Black
(--- ) 12VDC**
Black
Not Used
Orange
Gray
0V (24VAC on no call)
Violet
Red
24VAC continuous
White
24VAC**
Yellow
(--- ) 12VDC*
Green
24VAC**
Not Used