Fujitsu AUXG18LRLB Technical Manual page 96

Cassette type
Hide thumbs Also See for AUXG18LRLB:
Table of Contents

Advertisement

 Outdoor unit installation in multi-row
Single parallel unit arrangement
500 or more
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no
obstacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation
efficiency.
CAUTION
!
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap.
If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold
climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might
become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and
a pedestal, or place the unit on a high stand that is locally installed.
100 or more
1,000 or more
200 or more
- 90 -
Multiple parallel unit arrangement
1,000 or more
Unit: mm
200 or more
2,000 or more
400 or more
200 or more

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents