Vivax ACP-56COFM164GEEI User Manual page 24

Table of Contents

Advertisement

3)
Example: ACP-56COFM164GEEI
Serial No.
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 4
Indoor unit 5
Indoor unit 6
Serial No.
L1
L2
L4
1A
1B
1C
2A
2B
2C
The total length of the liquid pipes: 20+10+10+5+5+5+5+5+5=70(m). Thus, the total
length is over than 30m, so the air conditioner needs to add refrigerant.
♦ Additional refrigerant charge
Fig. 19
Table 6
Cassette type
Duct type
Wall mounted type
Duct type
Duct type
Wall mounted type
Table 7
Diameter(mm)
Φ
9.52
Φ
9.52
Φ
9.52
Φ
6.35
Φ
6.35
Φ
6.35
Φ
6.35
Φ
6.35
Φ
6.35
19
Model
ACP-12CCIFM35GEEI
ACP-09DTIFM25GEEI
ACP-09CIFM25GEEI
ACP-09DTIFM25GEEI
ACP-09DTIFM25GEEI
ACP-09CIFM25GEEI
Length(m)
20
10
10
5
5
5
5
5
5

Hide quick links: