Flaring Work And Connection Of Piping - Kelvinator KSE88HRB Installation Manual

Hide thumbs Also See for KSE88HRB:
Table of Contents

Advertisement

Installation
Indoor unit outline
12cm or more
to wall
45
Left rear side
refrigerant
pipe hole 65
<(3.5kw) model: (A: 710, B: 250/ A:790, B:265)
(3.5kw) model: (A: 790, B:265)
15cm or more to ceiling
Indoor unit outline
12cm or more
to wall
45
Left rear side
refrigerant
pipe hole 65
80
(
Hooked Part
380
12cm or more
to the wall
130
(>(6.2kw)model)
Above 15cm to
the ceiling
178
Above 12cm to
the wall
Pipe hole
58
(7.0kw) and (8.0kw) model)
2. Drill a hole in the wall
1
Determine hole positions according to the diagram
φ
detailed above as applicable. Drill one (1) hole (
85mm
φ
for 2.6kW and 3,5kW models or
115mm for 5.3kW,
6.2kW, 7kW and 8kW models) slightly to outdoor side.
2
Always use wall hole conduit when drilling metal grid,
metal plate or the like.
8 installation Kelvinator Air Conditioning
15cm or more to ceiling
Installation plate
12cm or more
to wall
90
Right rear side
refrigerant
pipe hole
65
A
Installation plate
12cm or more
to wall
90
Right rear side
refrigerant
pipe hole
65
489
850
(3.5kw) model,
<(6.2kw) model
)
15cm or more to the ceiling
998
380
119
12cm or more
to the wall
130
Indoor Unit Outline
Hooked Part Hooker Part
1250
815
257
Above 12cm to
the wall
55
Pipe hole
Indoor unit outline
Wall
Outdoor
Indoor
Flaring work and connection
of piping
1
Flaring work
The main cause for gas leakage is due to defects in flaring
work. Carry out flaring work using the following procedure.
A
Cut the pipes and the cable.
Use the piping kit accessory (if applicable) or the pipes
purchased locally.
Measure the distance between the indoor and the
outdoor unit.
Cut the pipes a little longer than measured distance.
Cut the cable 1.5m longer than the pipe length.
B
Burrs removal
Completely remove all burrs from the cut cross section
of pipe/tube.
Place the end of the copper tube/pipe in a downward
direction as you remove burrs in order to avoid dropping
burrs into the tubing.
C
Putting flare nut on
Flare nut
Remove flare nuts attached to indoor and outdoor
unit, then put them on pipe/tube having completed
Burr removal, B.
Copper tube
Flare nut
Flare nut
Copper tube
Copper tube
Note: It is not possible to put them on after flaring work.
D
Flaring work
Carry out flaring work using flaring tool as shown below.
Ensure the flaring tool is suitable for R410 refrigerant and
in good condition. Refrigerant leaks from poorly made
flares are not covered by the product warranty.
A(mm)
Outer diam.
Max.
Min.
Flare nut
1/4" (6.35mm)
1.3
0.7
Copper tube
3/8" (9.53mm)
1.6
1.0
1/2" (12.7mm)
1.8
1.0
5/8" (16.0mm)
2.4
1.8
3/4" (19.0mm)
7.5
8.0
Hold copper pipe firmly in a die according to the dimension
show in the table above.
E
Check
Compare the flared work with the adjacent diagram.
If flare is found to be defective, cut off the flare section
and do flaring work again.
2
Connection of pipes – Indoor
Prepare the indoor unit's piping and drain hose for
installation through the wall.
Remove the tubing retainer (see illustration below) and
pull the tubing and drain the hose away from chassis (if
required). For some models this is not needed.
Replace the tubing retainer in its original position.
Kelvinator Air Conditioning flaring work and connection 9

Advertisement

Table of Contents
loading

Table of Contents