Appendix F - Event Classification - Dranetz PowerGuide 4400 User Manual

Power quality analyzer
Hide thumbs Also See for PowerGuide 4400:
Table of Contents

Advertisement

Range of
Variations as per
IEEE, IEC, and
Dranetz
1.800.561.8187
A P P E N D I X
Event Classification
Events characterization implemented in the 4400 adheres to the IEEE 1159 and IEC
61000-4-30 Class A measurement standards. The range of variations as per IEEE and
IEC standards are featured below, along with quality test measurements developed by
Dranetz.
IEEE 1159
Short Duration Variations
Magnitudes
Sag/Dip
(Sag) Vrms Below 90%
(or Low limit) to 10% of
nominal
Swell
Vrms Above 110% (or
High limit) to 180% of
nominal
Interruption
Vrms Below 10% (or
Very Low limit) of
nominal
Temporal
Instantaneous
0.5 - 30 cycles
Momentary
0.5 - 30 seconds
Temporary
3 - 60 seconds
Duration
begins when any one
phase is Out of Limits;
ends when all phases are
Within Limits
Long Duration Variations
Magnitudes
Sag
same magnitude values
Swell
as Short Duration
Interruption
Variations (see above)
Duration
Sustained
> 1 minute
Cold Load
Pickup is return
from sustained
www.
F
IEC 61000-4-30
(deviations from IEEE
1159 only are noted)
(Dip) Vrms Below 90%
(or Low limit) of
nominal
Vrms Above 110% (or
High limit) of nominal
Vrms Below 1% (or
Very Low limit) of
nominal
information@itm.com
.com
Dranetz
Continued on next page
F-1