Fan Cycle/Continuous - Cool
When this switch is enabled (UP), it allows the indoor fan to cycle
on/off with the compressor. When this switch is disabled (DOWN),
it allows the indoor fan to run continuously. The default setting is
DOWN (continuous).
Fan Cycle/Continuous - Heat
When this switch is enabled (UP), it allows the indoor fan to cycle
on/off with the heater operation. When this switch is disabled
(DOWN), it allows the indoor fan to run continuously. The default
setting is UP (cyclic).
Class 2 - Remote Thermostat
When this switch is enabled (UP), it allows the unit to operate with
a Class 2 Remote Control Wall Thermostat. The unit controls are
disabled. The default setting is DOWN (disabled).
Terminal Connections Remote Thermostat - Class 2 (on some models)
The controls are located under a plastic cover behind the front
grille.
1. Remove the front grille. See the Front Grille section of Care
and Cleaning.
2. Remove the screws securing the plastic cover over the wiring
connections. Set aside screws and plastic cover.
3. To make wiring connections, insert the wires into the bottom
of the terminals and tighten screws securely.
4. After all desired connections have been made, replace the
plastic cover and front grille.
The owner is responsible for making all connections and setting
the appropriate dip switches.
When connected, the unit will be controlled by a remote
thermostat.
NOTE: The number 3 dip switch must be in the enabled (UP)
position to activate the remote thermostat. (See the installation
instructions supplied with the remote thermostat.)
IMPORTANT:
The thermostat connections provide 24 V AC only.
If using a digital/electronic wall thermostat, ensure it is
compatible with 24 VAC signal. See the Installation Instructions
for the wall thermostat.
NOTICE:
Damage to a wall thermostat or to the electronics can result
from improper connections. Special care must be used in
connecting the wires. No line voltage connections should be
made to any circuit. Isolate all wires in building from line voltage.
Fan Cycle/Continuous - Cool
Fan Cycle/Continuous - Heat
Class 2
Red - 24 V AC only
Green - Low Speed Fan
Green - High Speed Fan
No Function
(reserved for furture use)
Yellow - Compressor
White - Heater
Common - Ground
No Function
(reserved for furture use)
Terminal
connections
location
under front
grille
9