INSTALLING CASSETTE TYPE
INDOOR UNIT
A. Schematic diagram of installation spaces
1500 Min.
Service access door
B. Select install location of the indoor unit
1. Obstruct should put away from the intake or outlet vent of the indoor unit so that the airflow can be
blown though all the room.
2. Make sure that the installation had accord with the requirement of the schematic diagram of installation
spaces.
3. Select the place where can stand 4 times of the weight of the indoor unit and would not increase the
operating noise and oscillate.
4. The horizontally of the installation place should be guaranteed.
5. Select the place where is easy to drain out the condensate water, and connect with outdoor unit.
6. Make sure that there are enough space for care and maintenance. Make sure that the height between
the indoor unit and ground is above 2.5 m.
7. When installing the suspender bolt, check if the install place can stand the weight 4 times of the unit's. If
not, reinforce before installation. (Refer to the install cardboard and find where should be reinforced).
Note:
There will be lots of lampblack and dust stick on the centric fan, heat exchanger and water pump in dining
room and kitchen, which would reduce the capacity of heat exchanger, lead water leakage and abnormal
operation of the water pump.
1500 Min.
Piping connection
Distance from wall side
500 Min.
100 Min.
1000 Min.
Service space
Clearance
10 to 20mm
H
Unit hight in false
ceiling
Unit hight
1500 Min.
3000 Min.
Piping connection
Service access door
100 Min.
500 Min.
Models
AMD 385
AMD 386
25
1500 Min.
Piping connection
Service access door
H (mm)
248
298
Fig. 1