Keyswitch Wiring - Bosch D9412GV4 Installation Manual

Hide thumbs Also See for D9412GV4:
Table of Contents

Advertisement

20
en | Diagrams
Cable
Overall
capacitance
cable
length
pF/ft
ft
< 17
7500
18
7500
19
7350
20
7000
21
6666
Table 3.2: Maximum cable length
Notice!
Use Non-shielded cable only.
Notice!
Maximum capacitance of 140nF (140,000 pf) per system. Contact the wire manufacturer for
the capacitance ratings of the wire being used.
3.6

Keyswitch Wiring

Figure 3.12: Keyswitch Wiring
Callout - Description
1 - Maintained keyswitch
2 - Momentary keyswitch
3 - Common
4 - Point Input
5 – End of Line (EOL) resistor*
6 - Open on a circuit arms the area
7 - Short on a circuit toggles the arming state
2016.07 | 04 | F.01U.291.483
Cable
Overall
capacitance
cable
length
pF/ft
ft
22
6363
23
6086
24
5800
25
5600
26
5385
UL Installation Guide
Cable
Overall
capacitance
cable
length
pF/ft
ft
27
5185
28
5000
29
4828
30
4700
31
4516
Cable
Overall
capacitance
cable
length
pFf/ft
ft
32
4400
33
4242
34
4100
35
4000
36
3800
Bosch Security Systens, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

D7412gv4

Table of Contents