TUF-2000F User Manual
If the positive totalizer is turned off, the positive totalizer value shown on the screen
is the value prior to its turn off
Display flow rate and NEG(negative) totalizer
M03
If the negative totalizer is turned off, the negative totalizer value shown on the
screen is the value prior to its turn off
Display date and time, flow rate. The date and time setting method is found in
M04
MENU60
M05
Display energy rate(instantaneous Caloric)and total energy (Caloric)
M06
Display temperatures, inlet T1, outlet T2
Display analog inputs, AI3/AI4, current value and its corresponding temperature
M07
or pressure or liquid level value
Display all the detailed error codes
M08
Display working condition and system error codes. 'R' stands for normal, others
refer to Chapter for details.
M09
Display today's total NET flow
Window for entering the outer perimeter of the pipe
M10
If pipe outer diameter is known, skip this menu and go to Menu 11to enter the outer
diameter
Window for entering the outer diameter of the pipe. Valid range:0 to 18000mm.
M11
Note: you just need to enter either the outer diameter in M11 or the peripheral in
M10
Window for entering pipe wall thickness
M12
You may skip the menu and enter inner diameter in M13 instead.
Window for entering the inner diameter of the pipe
M13
If pipe outer diameter and wall thickness are enter correctly, the inner diameter will
be calculated automatically, thus no need to change anything in the window
Window for selecting pipe material
Standard pipe materials (no need to enter material sound speed ) include:
M14
(0) carbon steel (1) stainless steel (2) cast iron
(5) PVC
(9) other( need to enter material sound speed in M15)
M15
Window for entering the pipe material speed, only for non-standard pipe materials
Window for selecting the liner material, select none for pipes without any liner.
Standard liner materials(no need to enter the liner sound speed) include:
M16
(1) Tar Epoxy (2) Rubber (3) Mortar
(6)Polystyrene (7) Polyester
(11) Other (need to enter liner sound speed in M17)
M17
Window for entering the non-standard liner material speed.
M18
Window for entering the liner thickness, if there is a liner
M19
Window for entering the ABS thickness of the inside wall of the pipe
Window for selecting fluid type
M20
For standard liquids(no need to enter fluid sound speed) include:
(0) Water
(6) aluminum
,(7) asbestos
(8) Polyethylene (9) Ebonite (10) Teflon
(1) Sea Water
(2) Kerosene
(3) ductile iron
(8) fiberglass
(4) Polypropylene (5) Polystryol
5
(4) copper