4.3 Transducers Installation
The transducers used by the TUF-2000 series ultrasonic flow meter are made of piezoelectric crystals both
for transmitting and receiving ultrasonic signals through the wall of liquid piping system. The measurement
is realized by measuring the traveling time difference of the ultrasonic signals. Since the difference is very
small, the spacing and the alignment of the transducers are critical factors to the accuracy of the
measurement and the performance of the system. Meticulous care should be taken for the installation of the
transducers.
Steps to the installation of the transducers
(1) Locate an optimum position where the straight pipe length is sufficient, and where pipes are in a
favorable condition, e.g., newer pipes with no rust and ease of operation.
(2) Clean any dust and rust. For a better result, polishing the pipe with a sander is strongly recommended.
(3) Apply adequate coupler to the spot where the transducers are to be installed and leave no gap between
the pipe surface and the transducers.
Extra care should be taken to avoid any sand or dust particles left between the pipe outer surface and the
transducers.
To avoid gas bubbles inside the upper part of the pipe, the transducers should be installed horizontally by
the side of the pipe.
4.3.1 Wiring diagram of transducer
4.3.2 Transducers Spacing
The spacing value shown on menu window M25 refers to the distance of inner spacing between the two
transducers. The actual transducers spacing should be as close as possible to the spacing value.
4.3.3 V-method Installation
V-method installation is the most widely mode for daily measurement with pipe inner diameters ranging
from 15 mm to 200 mm. It is also called reflective mode.
17