Mitsubishi Electric FR-D700 Installation Manuallines page 24

Hide thumbs Also See for FR-D700:
Table of Contents

Advertisement

To use the inverter outside of an enclosure in the environment of pollution degree 2, fix a fan cover with fan cover fixing
screws enclosed.
FR-D740-080 or less
FR-D720S-070 and 100
Example for FR-D740-036
Note, the protection structure of the Inverter units is considered to be an IP00.
∗ On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C.
∗ The operating capacity of the relay outputs (terminal symbols A, B, C) should be 30VDC, 0.3A. (Relay outputs are
basically isolated from the inverter internal circuit.)
∗ Control circuit terminals on page 4 are safely isolated from the main circuit.
∗ Environment
Surrounding air
-10°C to +50°C
temperature
Humidity
90% RH or less
Maximum Altitude
Details are given in the technical information "Low Voltage Directive Conformance Guide" (BCN-A21041-203). Please contact your sales
representative.
∗ Provide the appropriate UL and cUL listed Class T type fuse that is suitable for branch circuit protection in accordance
with the table below.
FR-D740-
Rated fuse voltage(V)
Without power factor
Fuse Maximum
improving reactor
allowable rating
With power factor
(A)∗
improving reactor
FR-D720S-
Rated fuse voltage(V)
Without power factor
Fuse Maximum
improving reactor
allowable rating
With power factor
(A)∗
improving reactor
∗ Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
Fan cover
fixing screw
Fan cover
Fan connector
Fan
Running
In Storage
-20°C to +65°C
90% RH or less
1000m
1000m
-EC
012
022
6
10
6
10
-EC
008
014
240V or more
15
20
15
20
FR-D740-120 or more
Fan cover
fixing screws
Example for FR-D740-160
During Transportation
-20°C to +65°C
90% RH or less
10000m
036
050
080
120
160
480V or more
15
20
30
40
70
10
15
25
35
60
025
042
070
100
20
30
40
60
20
20
30
50
Fan cover
Fan
Fan connector
21

Hide quick links:

Advertisement

Table of Contents
loading