To access the Burner control box diagnostics or to use the burner reset
button to reset the burner, the burner diagnostic mode must be
activated as follows:
Burner LOCKOUT
Blue light flashing & 9F 855 cause
code on display (there is no power to
the burner when the controls are in
lockout.
Normal operation.
Fig. 89
The burner diagnostics mode can be manually exited at any time when the burner is locked out by holding down the service mode button
whilst pressing the controls reset button.
Fault code 9F 856: If burner lockout is reset 5 times in one demand period using the fascia reset button the controls will lockout with a new code: 9F
856. This is to protect the burner components against over use of the reset and requires a power down of the appliance to reset. The burner control box
also has this facility, if the reset button is operated 5 times the control box will not reset until the power has been interrupted to the burner.