Cause And Fault Codes - Worcester Greenstar Heatslave II 12/18 Installation, Commissioning & Servicing Instructions

Floor standing oil fired condensing combination boiler balanced flue
Table of Contents

Advertisement

8.4.3

Cause and fault codes

Cause
Fault
code
code
Description
210
E9
Max temperature thermostat activated
212
No
Safety or flow temperature rises too high
code
218
E5
Flow temperature too high
219
E9
Safety temperature too high
220
E9
Safety sensor short circuit
221
E9
Safety sensor open circuit
222
E2
Flow sensor short circuit
223
E2
Flow sensor open circuit
233
E2
HCM (Heat Control Module)
237
F0
238
F0
239
F0
Watchdog error
259
FO
AD reference error
263
F0
Appliance powered off with locking fault
present
271
D4
Temperature difference between flow
and safety sensors exceeds limit
276
E9
Flow temperature exceeds 95°C
277
E9
Safety temperature exceeds 95°C
278
F0
Sensor test error
279
F0
AD converter error
290
F0
AD converter reference error
332
E5
Primary flow has exceeded 105°C
359
No
DHW outlet or storage tank exceeds 90°C
Code
360
9A
Incorrect HCM for boiler variant
380
No
Inlet DCW temperature higher than DHW
code
outlet temperature
808
A7
DHW sensor defective
809
A0
Thermal store sensor defective
855
9F
Burner lock out
856
9F
5 burner lockouts repeated resets
Table 15 Cause and fault codes
H code Displayed symbols
H03
Warning triangle and House symbol displayed on controller
H11
Warning triangle symbol displayed on controller
Table 16 H fault codes
Greenstar Heatslave II External
ErP -
6 720 813 345 (2014/09)
Reset
type
Blocking Locking
Reset
Flue gas or tank thermostat overheat. Reset the overheat
X
thermostat before resetting the appliance.
X
Air lock or reduced water content.
X
Reset
Primary sensor overheated.
X
Reset
The main heat exchanger has overheated.
Maximum temperature 105°C.
X
Reset
Maximum temperature sensor on the main heat exchanger has
failed.
X
Reset
Maximum temperature sensor on the main heat exchanger has
not been recognised.
X
Reset
Flow sensor shorted or damaged.
X
Reset
Flow sensor disconnected or damaged.
X
Reset
HCM Code plug missing or defective.
Resistors between plug X4 pins 3 & 5 disconnected/>150k 
X
Reset
or water in the burner control box
Resistors between plug X4 pins 3 & 5 disconnected/>150k 
X
Reset
or water in the burner control box
X
Reset
X
Reset
X
Reset
Locking fault present when powered off.
X
The temperature of the primary flow and the safety sensor on
the main heat exchanger should be within 15°C of each other.
X
Primary overheat - boiler waits for temperature to reduce,
approximately 30 minutes.
X
Main heat exchanger safety sensor overheat - boiler waits for
temperature to reduce, approximately 30 minutes.
X
Reset
On power up, all safety sensors are checked. Check has failed.
X
Reset
X
Reset
X
Reset
Primary sensor overheated.
X
Pump & burner are blocked until temperature drops to <89°C.
X
X
The output is blocked until the inlet temperature drops below
the output temperature.
X
Reset
X
Reset
X
Reset
Check the burner and fuel supply. Ensure the oil supply is free
of contaminants.
X
Turn
After Five 855 burner lock outs in one demand period, cause
boiler
code 856 is displayed.
off/on
After boiler off/on cause code 263 will be displayed, press the
reset button to clear this fault. another 5 burner lock resets can
be attempted.
Cause
Weather compensation activated but no weather sensor detected,
refer to section 5.11 on page 24 for more information.
DCW in sensor defect, (appliance operation not affected)
Fault finding and diagnosis