This section explains each part name of the CC-Link safety relay module.
Number
1)
Indicator LED
5
- 9
5.2 CC-Link Safety Relay Module

5.2.3 Part names and settings

Part names and settings
Figure 5.4 CC-Link safety relay module
Table 5.2 Part names (1/2)
Name
PW
ERR.
L RUN
SD
RD
L ERR.
S PW
3)
8)
1)
7)
11)
2)
Indicates status of the module power supply.
ON:
Module power supply is supplied.
OFF:
Module power supply is cut off or powered OFF with electric fuse.
Indicates a failure in the monitor function of a module or an error in
communications with the extension module.
ON:
An error occurred in communications with the extension safety relay
module.
OFF:
Normal
Indicates communicaiton status of the CC-Link system.
ON:
Normal communication
OFF:
Communication is cut off (time over error).
ON:
During data transmission
ON:
During data reception
Indicates a communication error in the CC-Link system.
ON:
A value set with station number setting switch or
transmission speed setting switch is out of range.
Flashing regularly:
The station number setting switch or transmission
speed setting switch is changed during operation.
Flashing irregularly: A terminating resistor is not attached, is attached
wrongly or is influenced by noise.
OFF:
Normal communication
Indicates communication status of safety part power supply.
ON:
Safety part power supply is supplied.
OFF:
Safety part power supply is cut off or powered OFF with electric fuse.
Description
6)
5)
1)
10)
9)
4)
6)