Check the elevation where your water heater is installed. Set your DIP switches according to altitude as
shown below.
Indoor models
Altitude
DIP switches
ON
OFF
110U (AT-KJr3U) and
310U (AT-K5U) models
ON 1 2 3 4 5 6
510U (AT-D3U) model
OFF
(Lower bank of
DIP switches)
Outdoor models
Altitude
DIP switches
ON
OFF
110U (AT-KJr3U) and
310U (AT-K5U) models
ON 1 2 3 4 5 6
510U (AT-D3U) model
OFF
(Lower bank of
DIP switches)
NOTE: The dark squares indicate the correct DIP switch positions.
110U (AT-KJr3U-IN/OS) and 310U (AT-K5U-IN/OS)
Computer board
Bank of DIP switches
HIGH-ALTITUDE INSTALLATIONS
2,001 to
0 to 2,000 ft.
3,000 ft.
(0 to 610 m)
(611 to 914 m)
(DEFAULT)
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
ON
OFF
No. 3 : OFF
No. 3 : OFF
No. 4 : OFF
No. 4 : ON
No. 5 : OFF
No. 5 : OFF
ON 1 2 3 4 5 6
OFF
No. 2 : OFF
No. 2 : OFF
No. 3 : OFF
No. 3 : ON
No. 4 : OFF
No. 4 : OFF
0 to 2,000 ft.
2,001 to
(0 to 610 m)
4,000 ft.
(DEFAULT)
(611 to 1,219 m)
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
ON
OFF
No. 3 : OFF
No. 3 : OFF
No. 4 : OFF
No. 4 : OFF
No. 5 : OFF
No. 5 : ON
ON 1 2 3 4 5 6
OFF
No. 2 : OFF
No. 2 : OFF
No. 3 : OFF
No. 3 : OFF
No. 4 : OFF
No. 4 : ON
12
3,001 to
5,001 to
5,000 ft.
7,500 ft.
(915 to 1,524 m)
(1,525 to 2,286 m)
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
ON
ON
OFF
OFF
No. 3 : OFF
No. 3 : OFF
No. 4 : OFF
No. 4 : ON
No. 5 : ON
No. 5 : ON
ON 1 2 3 4 5 6
ON 1 2 3 4 5 6
OFF
OFF
No. 2 : OFF
No. 2 : OFF
No. 3 : OFF
No. 3 : ON
No. 4 : ON
No. 4 : ON
4,001 to
6,000 ft.
Installation altitude
(1,220 to 1,829 m)
The maximum certified or
1 2 3 4 5 6 7 8 9 10
ON
allowable installed altitude
OFF
is 10,100 ft. (3,078 m) for
No. 3 : ON
No. 4 : OFF
indoor models and 6,000
No. 5 : ON
ft. (1,829 m) for outdoor
ON 1 2 3 4 5 6
models.
OFF
No. 2 : ON
No. 3 : OFF
No. 4 : ON
510U (AT-D3U-IN/OS)
Computer board
Lower bank of DIP switches
Page
Installation Manual
Installation
7,501 to
10,100 ft.
(2,287 to 3,078 m)
1 2 3 4 5 6 7 8 9 10
ON
OFF
No. 3 : ON
No. 4 : ON
No. 5 : ON
ON 1 2 3 4 5 6
OFF
No. 2 : ON
No. 3 : ON
No. 4 : ON