Takagi AT-KJr3U-IN Installation Manual And Owner's Manual page 17

On-demand water heaters series 200
Table of Contents

Advertisement

Calculate minimum size of vent openings and ducts
The vent cross-sectional area needed to provide the free area depends on the covering on the vent openings. Typical
vents use louvers or grilles to protect the opening. The louver or grill itself blocks some of the free area, so the open-
ing may need to be larger to meet the minimum free area requirements.
Use the following formula to calculate the required cross-sectional area:
Cross-sectional area = minimum free area required ÷ percent free area of covering (in decimals – e.g., 60% = 0.6)
For example, an installation area that requires openings with 100 square inches of free area would need
134 square inch openings if using metal louvers rated at 75% free area (100 sq. in. ÷ 0.75 = 134 sq. in.).
If you do not know the % free area for your louver or grill, use the following values:
For wood louvers or grilles: 25%
For metal louvers or grilles: 75%
Follow these rules to ensure that vents and ducts provide adequate air flow:
Each vent opening must be no smaller than 100 square inches .
Ducts must have the same cross-sectional area as free area of the opening.
Rectangular ducts must have a minimum dimension of no less than three inches .
All screens must have mesh ¼" or larger.
Moveable louvers must be locked open or interconnected with the equipment so that they open automati-
cally during operation.
Keep louvers and grills clean and free of debris or other obstructions.
Check that air source is clean and free of chemicals
Air for combustion and ventilation must be clean and free of corrosive or flammable chemicals. A failure due to cor-
rosive chemicals in the air is not covered by the warranty. Combustion air must be free of acid-forming chemicals such
as sulfur, fluorine, and chlorine. Be sure that air at the vent inlets is free of such chemicals.
Table 1
Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply – Air from outdoor or
indoor spaces.
Based on the total BTU/h input rating for all gas burning appliances within a confined space.
Opening Source
Direct to outdoors*
Vertical ducts
Horizontal ducts
Single Opening
Two permanent openings
to another room**
*These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through
an outside wall.
** For direction on combining spaces in different stories within the structure, refer to the current edition of the
National Fuel Gas Code ANSI Z223.1/NFPA 54.
See graphics on next page.
Minimum Free Area
1 sq. in. per 4,000 BTU/hr (see Figure 1, 2)
1 sq. in. per 4,000 BTU/hr (see Figure 3)
1 sq. in. per 2,000 BTU/hr (see Figure 4)
1 sq. in. per 3,000 BTU/hr (see Figure 5)
1 sq. in. per 1,000 Btu/hr (see Figure 6)
Opening: 100 in.
MIN.
2
Minimum dimension of air openings:
no less than 3 in.
17
Page

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

At-k5u-inAt-kjr3u-osAt-k5u-osAt-d3u-inAt-d3u-os

Table of Contents