Wiring the FM 352

5.4 Terminal assignment of the front connector

5.4
Terminal assignment of the front connector
Front connector
You connect the power supply and the switching elements by wiring these to the front
connector.
Terminal assignment of the front connector
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Auxiliary voltage for encoders and digital outputs (L+, M)
The 24 V DC auxiliary voltage of the encoders and digital outputs is monitored:
● for wire-break of the 24 V feed line
● for power failure
The 24 V DC auxiliary supply is converted internally to 5.2 V DC. This supplies 24 V DC and
5 V DC at the encoder interface (sub D socket X2) to the various types of encoders.
The general technical data and requirements for the DC load power supplies are described
in the Operating Instructions SIMATIC S7-300 CPU 31xC and CPU 31x: Installation
(http://support.automation.siemens.com/WW/view/en/13008499).
32
Name
Meaning
L+
24 V DC encoder supply, and digital outputs
M
Ground of the encoder supply and digital outputs
I 0
Brake enable
I 1
Length measurement/ edge detection/ set actual value on-the-fly
I 2
Home position switch
I 3
Enable track signal 3
Q 0
Digital output 0
Q 1
Digital output 1
Q 2
Digital output 2
Q 3
Digital output 3
Q 4
Digital output 4
Q 5
Digital output 5
Q 6
Digital output 6
Q 7
Digital output 7
Q 8
Digital output 8
Q 9
Digital output 9
Q 10
Digital output 10
Q 11
Digital output 11
Q 12
Digital output 12
- - -
- - -