Carrier 50TC*D17 Series Installation Instructions Manual page 30

Single package rooftop, 50hz cooling only with novation coil sizes 17, 20, 24, 28 with puron (r-410a) refrigerant
Hide thumbs Also See for 50TC*D17 Series:
Table of Contents

Advertisement

Remote Occupancy
The remote occupancy accessory is a field- - installed
accessory. This accessory overrides the unoccupied mode
and puts the unit in occupied mode. When installing this
accessory, the unit must be configured for remote
occupancy by setting MENU
5, 8, or 9 to Remote Occupancy and normally open (N/O)
or normally closed (N/C).
Also set MENU
Schedules
on/off. Input 8 or 9 is recommended for easy of
installation. Refer to Fig. 43 and Table 9 for wire
terminations at J5.
Power Exhaust (output)
Connect the accessory Power Exhaust contactor coil(s) per
Fig. 51.
Power Exhaust
PEC
TAN
GRA
Fig. 51 - - RTU- - MP Power Exhaust Connections
PROTOCOL
DS8
BACnet MS/TP
Unused
(Master)
Modbus
Unused
(Slave)
N2
Unused
(Slave)
LonWorks
Unused
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
Baud Rate Selections
BAUD RATE
9600
19,200
38,400
76,800
Config
Inputs
input 3,
occupancy source to DI
J11-3
CTB
THERMOSTAT
C
C08464
SW3 Protocol Selection
DS7
DS6
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
DS2
DS1
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Fig. 52 - - RTU- - MP SW3 Dip Switch Settings
Space Relative Humidity Sensor - - The RH sensor is not
used with 50TC*D models at this time.
Communication Wiring - - Protocols
General
Protocols are the communication languages spoken by
control devices. The main purpose of a protocol is to
communicate information in the most efficient method
possible. Different protocols exist to provide different
kinds of information for different applications. In the BAS
application, many different protocols are used, depending
on manufacturer. Protocols do not change the function of
a controller; just make the front end user different.
The RTU- - MP can be set to communicate on four different
protocols: BACnet, Modbus, N2, and LonWorks. Switch 3
(SW3) on the board is used to set protocol and baud rate.
Switches 1 and 2 (SW1 and SW2) are used to set the
board's network address. See Fig. 52 for the switch setting
per protocol. The 3rd party connection to the RTU- - MP is
through plug J19.
NOTE: Power must be cycled after changing the SW1- - 3
switch settings.
Refer to the RTU- - MP 3rd Party Integration Guide for
more detailed information on protocols, 3rd party wiring,
and networking.
DS5
DS4
DS3
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
30
DS2
DS1
Select Baud
Select Baud
Select Baud
Select Baud
OFF
OFF
OFF
OFF
C07166

Advertisement

Table of Contents
loading

This manual is also suitable for:

50tc*d20 series50tc*d24 series50tc*d28 series