Events requiring FRU replacements

Table 1 Events requiring FRU replacements scenarios
Event ID
FRU
8
HDD
39
Controller
40
Controller
50
Controller
51
Controller
55
HDD
58
HDD
62
HDD
65
Controller
95
Controller
157
Controller
204
CompactFlash
217
Controller
Symptom
See
"Disk Error Conditions and Recommended Actions" (page 12)
The sensors monitored a
temperature or voltage in the
warning range.
The sensors monitored a
temperature or voltage in the
failure range.
Correctable ECC error in buffer
memory.
An uncorrectable ECC error
occurred in buffer memory.
A disk drive reported a SMART
event.
A disk drive detected a serious
error, such as a parity error or
disk hardware failure.
The indicated global or
dedicated spare disk has failed.
The drive LED changes to
amber.
An uncorrectable ECC error
occurred on the buffer memory
on startup.
Both controllers in an
Active-Active configuration have
the same serial number.
A failure occurred when trying to
write to the Storage Controller
flash chip.
A failure occurred when trying to
write to the CompactFlash.
A supercapacitor failure occurred
on the controller.
Action Required
Verify the following:
The system has two power supplies and both
are running correctly
The ambient temperature is not too warm. The
enclosure operating range is 5–40°C
(41°F–104°F)
A module or blank plate resides in every module
slot in the enclosure
If none of these conditions apply, replace the
controller module that reported the error.
Verify the following:
The system has two power supplies and both
are running correctly
The ambient temperature is not too warm. The
enclosure operating range is 5–40°C
(41°F–104°F)
A module or blank plate resides in every module
slot in the enclosure
If none of these conditions apply, replace the
controller module that reported the error.
Replace on multiple occurrences.
Replace on first occurrence.
Replace on first occurrence.
Replace on first occurrence.
Replace the drive.
Replace on first occurrence.
Replace one of the controllers on first occurrence.
Replace on first occurrence.
Replace the CompactFlash.
Replace on first occurrence.