GE 345 Quick Start Manual page 79

Transformer protection system
Hide thumbs Also See for 345:
Table of Contents

Advertisement

CHAPTER 4: QUICK SETUP - FRONT CONTROL PANEL
345 TRANSFORMER PROTECTION SYSTEM – QUICKSTART GUIDE
GND CT INPUT
Range: CT(W1), CT(W2)
Default: CT(W1)
GND TOC1 PICKUP
Range: 0.05 to 20.00 x CT in steps of 0.01 x CT
Default: 1.00 x CT
GND TOC1 CURVE
Range: ANSI Extremely/Very/Moderately/Normally Inverse, Definite
Time, IEC Curve A/B/C and Short Inverse, IAC Extremely/Very/Inverse/
Short
Default: Ext. Inverse
GND TOC1 TDM
Range: 0.05 to 20.00 in steps of 0.01
Default: 1.00
RLY1 TRIP W1 BKR
Range: Do not operate, Operate
Default: Do not operate
RLY2 TRIP W2 BKR
Range: Do not operate, Operate
Default: Do not operate
PH IOC1 FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
PH CT INPUT
Range: CT(W1), CT(W2)
Default: CT(W1)
PH IOC1 PICKUP
Range: 0.05 to 20.00 x CT in steps of 0.01 x CT
Default: 1.00 x CT
RLY1 TRIP W1 BKR
Range: Do not operate, Operate
Default: Do not operate
RLY2 TRIP W2 BKR
Range: Do not operate, Operate
Default: Do not operate
GND IOC FUNCTION
Range: Disabled, Trip, Latched Alarm, Alarm
Default: Disabled
GND CT INPUT
Range: CT(W1), CT(W2)
Default: CT(W1)
GND IOC1 PICKUP
Range: 0.05 to 20.00 x CT in steps of 0.01 x CT
Default: 1.00 x CT
QUICK SETUP MENU
73

Advertisement

Table of Contents
loading

Table of Contents