Power Supply - GE 345 Quick Start Manual

Transformer protection system
Hide thumbs Also See for 345:
Table of Contents

Advertisement

CHAPTER 1: INTRODUCTION

Power supply

345 TRANSFORMER PROTECTION SYSTEM – QUICKSTART GUIDE
FORM-A RELAYS
Configuration:....................................................... 2 (two) electromechanical
Contact material: ................................................ silver-alloy
Operate time:........................................................ <8 ms
Continuous current:........................................... 10 A
Make and carry for 0.2s:.................................. 30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):................. 24 V / 1 A
Break (DC resistive):............................................ 24 V / 10 A
Break (AC inductive): .......................................... 720 VA @ 250 VAC Pilot duty A300
Break (AC resistive): ............................................ 277 VAC / 10 A
FORM-A VOLTAGE MONITOR
Applicable voltage:............................................. 20 to 250 VDC
Trickle current:...................................................... 1 to 2.5 mA
FORM-C RELAYS
Configuration:....................................................... 5 (five) electromechanical
Contact material: ................................................ silver-alloy
Operate time:........................................................ <8 ms
Continuous current:........................................... 10 A
Make and carry for 0.2s:.................................. 30 A per ANSI C37.90
Break (DC inductive, L/R=40 ms):................. 24 V / 1 A
Break (DC resistive):............................................ 24 V / 10 A
Break (AC inductive): .......................................... 720 VA @ 250 VAC Pilot duty A300
Break (AC resistive): ............................................ 277 VAC / 10 A
TRIP SEAL-IN
Relay 1 trip seal-in:............................................. 0.00 to 9.99 s in steps of 0.01
Relay 2 trip seal-in:............................................. 0.00 to 9.99 s in steps of 0.01
HIGH RANGE POWER SUPPLY
Nominal:.................................................................. 120 to 240 VAC
Range: ...................................................................... 60 to 300 VAC (50 and 60 Hz)
Ride-through time: ............................................. 35 ms
LOW RANGE POWER SUPPLY
Nominal:.................................................................. 24 to 48 VDC
Range: ...................................................................... 20 to 60 VDC
ALL RANGES
Voltage withstand: ............................................. 2 × highest nominal voltage for 10 ms
Power consumption: ......................................... 15 W nominal, 20 W maximum
Fuse rating: ............................................................ 5A fuse; time lag, slow blow, 350V 4.5 O.D. X 14.5mm
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
48 V / 0.5 A
125 V / 0.3 A
250 V / 0.2 A
48 V / 6 A
125 V / 0.5 A
250 V / 0.3 A
125 to 250 VDC
84 to 250 VDC
20 VA nominal, 28 VA maximum
SPECIFICATIONS
11

Advertisement

Table of Contents
loading

Table of Contents